100kva - 500kva    
     

 

 

The MPG Series generators are complete, stand alone, generating sets, all models consist of branded alternator which is directly coupled to a diesel engine Isuzu 4JB1. Isuzu 4JB1 engine is applied a very mature technology, for many years, until now this engine is used for Komatsu and TCM Forklifts. Spare Parts are easy available in market.

 

Download Catalouge Click Here

 
 

PERFORMANCE FEATURES

MPG- 30-IS / MPG-35-IS is using Isuzu 4JB1 Engine, this engine is a very mature Technology, Currently this engine is used for Fort Lift ( TCM, KOMATSU). Spare Parts are available in Market.

High Quality Fuel Injection
4JB1 Isuzu Engine equipped with High Quality Fuel Injection nozzle

High Performance Power Supply
Voltage Regulation- ±1.5%
Frequency Regulation-  < 5.0% through no load to full load
Voltage Waveform: Deviation Factor of open circuit terminal voltage does not exceed 0.06
Telephone influence Factor (TIF) is less than 50.
Electromagnetic Interference Level: Attenuated to meet most commercial requirement
MPG Generator provides Clean Power Quality supply, most suitable for sensitive load example: switching devices, Telecommunication equipments, Computer system. Various of Testing have been proven our High Performance Power Quality Supply.

Easy Maintenance
The large doors gives you full access all parts of Engine & alternator, Special designed Stainless Steel Revel allows you to moved out all the doors easily.External Drain Plugs for oil, fuel & water are fitted allowed you to perform routine maintenance.

Digital Controller
Provide you all the important measurements & Display Parameters-
( 3 Ø Volts , 3 L-L Volts, 3 Ø Load Current,  Hz, 3 Ø Complex Power, 3 Ø Real
Power, 3 Ø Reactive Power, 3 Ø Pf, Kwh, KAvrh, RPM, Kpa, Gen Water 
Temperature, Fuel Level %, Battery Volts, Gen Run Hours)
Provide you a complete Generator Protection
(Over water Temperature (Alarm/Stop), Low Oil Pressure (Alarm/Stop),
Over speed (Alarm/Stop), Under/ Over Hz (Alarm/Stop), Under / Over Voltage
(Alarm/Stop), Charge Fail, Fail to Start, E.Stop
ATS (Automatic Transfer Scheme Function
Once main supply failure, Generator will start up itself and change over to generator supply with minimum interruption.
Extra I/O
It provides Gen Remote Start Function, and 3 undefined I/O control

Electrical Protection
We are using branded Electrical devices to make sure stability of electrical protection & Complied BS & IEC safety standards.(Omron Earth Leakage Relay, & Merlin Gerlin MCCB).

Environmental Friendly
MPG Generator was built with Special sound proof material, especially in bungalows & town areas usage, there is a demand of low noise pollution. The MPG generator is extremely quiet even at the full load condition.

Safety  Solid Canopy design
We are concerning every safety precautious, every parts of generator we designed, we think of safety precautious, Example: Extra Bracket was built to prevent engine & alternator turning over, Exhaust Cover to prevent raining water get into exhaust, Engine Diesel Tank inlet was built at side way is a better way to cleaning your diesel oil waste, Water Proof steel canopy, Electronic Soleniod control to Start/Stop Engine. 

Balance point lifting hook
Built on the top of each generators, to facilitates easy transportation handling using crane or forklift.

 
 
Gensets Model MPG-30-IS MPG-35-IS
SET Rated power(KW/kVA) 20/25 25/31
Max.power(kw/kVA) 22/27.5 26.5/33
Frequency(Hz) 50 50
Noice level for silent type (Db) 65/7M 65/7M
Controller Digital Digital
ENGINE Engine Water Cooled Industrial Engine
Model type 4JB1
Isuzu
4JB1T
Isuzu
Max Output (1500rpm/ 1800rpm) 27/31KW 32/36.5KW
Rated Output (1500rpm/ 1800rpm) 24/28KW 28/34KW
Cylinders 4 4
Bore×stroke(mm) 93×102 93×102
Intake Method Nature Intake Nature Intake
Displacement(L) 2.8 2.8
Fuel consumption (ℓ/Hr) 4.8 ℓ/ Hr 5.3 ℓ/Hr
Cooling starting method Electric start Electric start
ALTERNATOR Stamford Model BCI184F BCI184G
Alternator manufacturer Stamford Stamford
Rated Power (50Hz/60Hz) 22Kw/27.5Kva
24Kw/30Kva
25Kw/31Kva
27.5/35Kva
Rated voltage(V) 400/415V ; 200/220V 400/415V ; 200/220V
Power factor(cosØ) 0.8(Lagging) 0.8(Lagging)
Phase  3-phase 3-phase
Excitation Self-exciting Self-exciting
Voltage regulation Automatic Automatic
Net weight(Silent type)(kg) 750 810
Packing size(silent type)L×W×H(mm) 1800*730*900 1800*780*900
Fuel Tabk Capacity (ℓ) 70ℓ 80ℓ
Other spare parts (1 piece) ① Air filter element ① Air filter element
②Diesel oil filter element ②Diesel oil filter element
③ Oil filters  ④Manual   ③ Oil filters  ④Manual  
⑤Special tool ⑤Special tool
Fuel Consumption above is based on operation at 75% load
engine is 210g/kw.h
so 24x210/900=5.75L/h at 100% load
5.75 L/Hours at full load 6.5L/Hours at full load
 
     